Honeywell Analytics Poole BH17 0RZ UK 2108B2001N Baseefa 13ATEX0964X POINT INFRARED GAS DETECTOR
- Condition: Used
- Brand: Honeywell
- Product Code: 2108B2001N
- SKU: #BD/21#
- Availability: 1
- Warranty term: 30 days
- Located in: Ukraine
HONEYWELL 2108B2001N BH170RZUK POINT INFRARED GAS DETECTOR 1 PCS #D7809#
Honeywell Analytics 2108B2001N gas detector:
Main Specifications (Hydrocarbon Optima Plus, 2108B2001N)
-
Type: Point-type infrared detector for flammable hydrocarbon gases.
-
Measurement range: 0–100% LEL, applicable to a wide range of hydrocarbon gases and vapors.
-
Output signal:
-
Analog: 4–20 mA (sink/source, auto-detect);
-
Digital (optional): Modbus RS‑485 or HART® over 4–20 mA.
-
-
Power supply: 18–32 VDC, power consumption approx. 8 W.
-
Housing material: 316 stainless steel.
-
Response time:
-
T₅₀ < 3 s, T₉₀ < 4 s (example: methane).
-
-
Accuracy:
-
Baseline error ±1% FSD;
-
Up to ±2% FSD at 50% of scale.
-
-
Repeatability: ±2% FSD (at 50% of scale); linearity < 5% FSD.
Environmental & Protection Ratings
-
Operating temperature:
-
Up to +55 °C with Tₘₐₓ = 86 °C;
-
Up to +65 °C with Tₘₐₓ = 96 °C.
-
-
Ingress protection: IP66/IP67.
Certifications
-
ATEX/UKEX: II 2 GD Ex db op is IIC Gb / Ex tb IIIC_Db.
-
IECEx, UL, FM/CSA, InMetro (Brazil), EAC (Eurasian Union), CCCF (China), and more.
Configuration and Options
-
Base model: 2108B2001N – Hydrocarbon Optima Plus (no HART).
-
Other variants: e.g., Ethylene (2108B2003), UL/FM versions (2108B2101 etc.).
-
Accessories: weather shields, calibration interfaces (SHC1), mounting kits, adaptors, and more.
Manufacturer
-
Manufacturer: Honeywell Analytics Ltd, Poole, BH17 0RZ, United Kingdom.
-
Weight: approximately 1.6–2.0 kg.
Application & Benefits
-
Ideal for harsh environments: oil & gas, refineries, terminals, gas stations, offshore, FPSO, LNG/LPG facilities, etc.
-
Infrared sensing ensures:
-
high reliability,
-
resistance to sensor poisoning,
-
low maintenance costs.
-
Summary for Model 2108B2001N (Hydrocarbon, no HART)
-
Type: Infrared point gas detector for hydrocarbons
-
Range: 0–100% LEL
-
Output:
-
4–20 mA analog,
-
Optional Modbus or HART
-
-
Power: 18–32 VDC, ~8 W
-
Housing: 316 stainless steel, IP66/67
-
Temp. range: –40°C to +55/+65°C
-
Response: T50 <3 s, T90 <4 s
-
Certifications: ATEX, IECEx, UL, FM, CSA, InMetro, EAC, CCCF, etc.
-
Weight: ~1.6–2.0 kg
On this page you will find the user manual for Searchpoint Optima Plus with optional HART® output. Get detailed technical specifications, installation and operating instructions to ensure optimum performance and reliability.
Manual for Searchpoint Optima Plus with optional HART® output
Related Products
CULLIGAN KRA GASKET O-RING VALVE 2" N.A. NORYL 2100383 #BD7809# (1 pcs)
$99.00 Ex Tax: $99.00
Honeywell 0854.611-73 Enraf 854 ATG SPU_II S0854611 0854.611 ( № 4 )
$745.00 Ex Tax: $745.00
Honeywell Enraf - NONIUS 854 ATG/XTG HPU 0854.644 REV.11 + OPA, S0854644 ( № 3 )
$1,170.00 Ex Tax: $1,170.00